Voltage | : | 400 VRMS | Phase | : | 3 |
|
Voltage Range | : | 320 ~ 480 VRMS | Frequency | : | 50/60 Hz |
|
Power | : | 0.00 kW | Current | : | 17.00 Arms |
|
Frequency (4 poles compressor) | : | Hz | Frequency (6 poles compressor) | : | Hz |
|
Carrier Frequency | : | 5 kHz,Power | Current | : | 30.00 Arms |
|
Frequency (4 poles compressor) | : | Hz | Frequency (6 poles compressor) | : | Hz |
|
Carrier Frequency | : | 5 kHz |
Voltage (Low) | : | 350 VDC | Voltage (High) | : | 700 VDC |
|
Current (Speed down) | : | 15.5 ARMS | Current S/W Trip | : | 16.5 ARMS |
|
Fin Temperature (Speed down) | : | 83 ℃ | Fin Temperature (Trip) | : | 86 ℃ |
|
Discharge Temperature (Speed down) | : | 110 ℃ | Discharge Temperature (Trip) | : | 115 ℃,Voltage (Low) |
|
Voltage (High) | : | 700 VDC | Current (Speed down) | : | 15.5 ARMS |
|
Current S/W Trip | : | 16.5 ARMS | Fin Temperature (Speed down) | : | 83 ℃ |
|
Fin Temperature (Trip) | : | 86 ℃ | Discharge Temperature (Speed down) | : | 115 ℃ |
|
Discharge Temperature (Trip) | : | 120 ℃,Voltage (Low) | Voltage (High) | : | 700 VDC |
|
Current (Speed down) | : | 17.5 ARMS | Current S/W Trip | : | 18.5 ARMS |
|
Fin Temperature (Speed down) | : | 83 ℃ | Fin Temperature (Trip) | : | 86 ℃ |
|
Discharge Temperature (Speed down) | : | 115 ℃ | Discharge Temperature (Trip) | : | 120 ℃,Voltage (Low) |
|
Voltage (High) | : | 700 VDC | Current (Speed down) | : | 32 ARMS |
|
Current S/W Trip | : | 33 ARMS | Fin Temperature (Speed down) | : | 67 ℃ |
|
Fin Temperature (Trip) | : | 70 ℃ | Discharge Temperature (Speed down) | : | 120 ℃ |
|
Discharge Temperature (Trip) | : | 125 (Depend on compressor models) ℃ |
Control Method | : | Sensorless Vector Control | Analog Input | : | 0-10 Vdc (minimum 0.1mA) |
|
Run/Stop | : | External switch (Dry contact NO, Current capacity > 3mA) | Emergency Stop | : | External switch (Dry contact NC, Current capacity > 20mA) |
|
Fault Alarm Output | : | Relay output (NO, 230Vac/ 30Vdc, 5A),Control Method | Analog Input | : | 0-10 Vdc (minimum 0.1mA) |
|
Run/Stop | : | External switch (Dry contact NO, Current capacity > 3mA) | Emergency Stop | : | External switch (Dry contact NC, Current capacity > 20mA) |
|
Fault Alarm Output | : | Relay output (NO, 230Vac/ 30Vdc, 5A) |
RUN LED (Green) | : | Blink while running, Light while idling | CTRL LED (Orange) | : | Blink while operated by S/W protection mode |
|
Fault LED (Red) | : | Blink while systematic fault |
Interface | : | Standard RS-485 | Protocol | : | MODBUS-RTU (Asynchronous half-duplex) |
|
Controller Address | : | 1 to 247 | Baud Rate | : | 1200, 2400, 9600, 19200 bps |
|
Data Length | : | 8 bit | Parity | : | none, odd, even |
|
Stop Bit | : | 1, 2 | Response delay time | : | < 3.5 Char (Minimum 1.75 ms),Interface |
|
Protocol | : | MODBUS-RTU (Asynchronous half-duplex) | Controller Address | : | 1 to 32 |
|
Baud Rate | : | 1200, 2400, 9600, 19200 bps | Data Length | : | 8 bit |
|
Parity | : | none, odd, even | Stop Bit | : | 1, 2 |
|
Response delay time | : | < 3.5 Char (Minimum 1.75 ms) |
Operation Temperature | : | -20 to +60C, 2 to 95%RH, (No condensing, No freezing) | Storage Temperature | : | -40 to +85C, 2 to 85%RH, (No condensing, No freezing), Storage period 1 year |
|
Safety | : | EN 60335-1, EN 60335-2-34 | EMC | : | EN 61800-3 Cat. C1 |
|
Harmonic | : | EN 61000-3-12 |